Zero Halogen Flame Retardant 110℃ Double Insulated Cable, 0.6/1kV
Application
These cables are used in power and switchboard fixed applications.
Standard
- AS 5000.1
- AS1125
- AS3808
Cable Construction
CONDUCTOR | Nominal 0.2mm stranded flexible plain copper wire to AS 1125 |
INSULATION | R -E-110 to AS3808 |
INSULATION COLOUR: | White |
SHEATH: | HFS-110-TP to comply with AS3808 |
SHEATH COLOURS: | Orange , Black - other colours available by request |
Technical Characteristics
CONDUCTOR SIZE MM2 | ELECTRICAL RESISTANCE @20.C |
CURRENT RAT`ING' AMPS 2 SINGLE CORES | VOLTAGE DROP MV 1AM AT MAX OPERATING TEMPERATURE | |
MM2 | OHM/KM | SINGLE PHASE | THREE PHASE | |
10 | 1.910 | 105 | 4.97 | 4.30 |
16 | 1.210 | 135 | 3.13 | 2.70 |
25 | 0.780 | 185 | 1.99 | 1.72 |
35 | 0.554 | 225 | 1.44 | 1.24 |
50 | 0.386 | 275 | 1.07 | 0.92 |
70 | 0.272 | 350 | 0.769 | 0.65 |
95 | 0.206 | 435 | 0.567 | 0.48 |
120 | 0.161 | 510 | 0.465 | 0.39 |
Cable Parameter
CONDUCTOR SIZE | NO.OF CORES | CONDUCTOR NO./ OD | NOMINAL INSULATION THICKNESS |
NOMINAL SHEATH THICKNESS |
NOMINAL O.D. | APPROX.CABLE WEIGHT |
MM2 | MM | MM | MM | MM | KG/100M | |
10 | 1 | 322/0.2 | 1.0 | 1.4 | 9.1 | 16.30 |
16 | 1 | 511/0.2 | 1.0 | 1.4 | 10.1 | 23.40 |
25 | 1 | 784/0.2 | 1.2 | 1.4 | 11.8 | 33.60 |
35 | 1 | 1120102 | 1.2 | 1.4 | 13.1 | 44.60 |
50 | 1 | 1568/0.2 | 1.4 | 1.4 | 14.9 | 62.50 |
70 | 1 | 2240/0.2 | 1.4 | 1.4 | 17.0 | 81 .80 |
95 | 1 | 3040/0.2 | 1.6 | 1.5 | 19.3 | 113.00 |
120 | 1 | 3800/0.2 | 1.6 | 1.5 | 20.8 | 137.40 |